Open Access Open Access  Restricted Access Subscription Access
Open Access Open Access Open Access  Restricted Access Restricted Access Subscription Access

Dynamic performance of distance relay for series compensated transmission lines using Real Time Digital Simulator (RTDSNsup>TM)


Affiliations
1 Junior Research Fellow, Central Power Research Institute, Bengaluru, Karnataka, 560080, India
2 Additional Director, PSD, Central Power Research Institute, Bengaluru, Karnataka, 560080, India
3 Professor, Department of Electrical Engineering, PESCE, Mandya, Karnataka, 560080, India
     

   Subscribe/Renew Journal


Series capacitors are installed in the power system for various reasons like to increase power transfer capacity, to improve the system stability, to reduce system losses, to improve voltage regulation and flexible power flow control. But it also affects the performance of the conventional distance relay and causes certain protection issues. This paper briefly discusses the problems like voltage inversion, current inversion, overreach and under reach during the fault conditions on the series compensated lines and how the distance relays can mal-operate, by using RTDSTM. Before installing the relay in the actual system, it is possible to make compromised settings for relay, by understanding its performance due to the above problems and prevent relay to be mal-operated.

Keywords

Distance relay, series capacitor, Metal Oxide Varistor (MOV),voltage inversion, current inversion, overreach, Real Time Digital Simulator (RTDSTM).
User
Subscription Login to verify subscription
Notifications
Font Size

Abstract Views: 195

PDF Views: 0




  • Dynamic performance of distance relay for series compensated transmission lines using Real Time Digital Simulator (RTDSNsup>TM)

Abstract Views: 195  |  PDF Views: 0

Authors

Boda Anilkumar
Junior Research Fellow, Central Power Research Institute, Bengaluru, Karnataka, 560080, India
A. Amruthakala
Additional Director, PSD, Central Power Research Institute, Bengaluru, Karnataka, 560080, India
P. S. Puttaswamy
Professor, Department of Electrical Engineering, PESCE, Mandya, Karnataka, 560080, India

Abstract


Series capacitors are installed in the power system for various reasons like to increase power transfer capacity, to improve the system stability, to reduce system losses, to improve voltage regulation and flexible power flow control. But it also affects the performance of the conventional distance relay and causes certain protection issues. This paper briefly discusses the problems like voltage inversion, current inversion, overreach and under reach during the fault conditions on the series compensated lines and how the distance relays can mal-operate, by using RTDSTM. Before installing the relay in the actual system, it is possible to make compromised settings for relay, by understanding its performance due to the above problems and prevent relay to be mal-operated.

Keywords


Distance relay, series capacitor, Metal Oxide Varistor (MOV),voltage inversion, current inversion, overreach, Real Time Digital Simulator (RTDSTM).



DOI: https://doi.org/10.33686/prj.v12i3.189272